Scope:
Cables are applied to fixed installation in the rated AC voltage 0.6/1 kV cable shaft with high fall and withstand large mechanical force and tension of the fixed places of transmission and distribution power lines.
Feature of product:
Features:
1 .Isulation Cores Identification follow color Sperations extruded.
2. Large Cross-section cable follow Fan-shaped desine, Stable Structure,light weight,small diameter.
3. High Chemical stability, not flame-retardant.
4. cables can withstand greater external mechanical forces and tension, simple laying and maintenance.
5 .Have good electrical properties and insulation.
6. Have excellent heat aging resistance and security
Schematic:
Technical Parameters:
1. Conductor DC resistance meet the GB / T3956-2008 required
2.The Properties of Finished Cables Insulation Can meet GB / T12706.1 requirement. And Should Withstand AC Voltage 3.5KV 5Minutes without breakdown.
Conditions of Use:
Conditions of Use:
1.The ambient temperature for installation/Laying is not below 0 ℃, the bending radius should be not less than 10 times of cable diameter.
2.The Long-term Max temperature of Cable Conductor should be not exceed 70 ℃.
3. The Max temperature of Cable Conductor should be not exceed 160 ℃ in short Circuit(the longest duration of no more than 5S and temperature is 140 ℃ when Cable section is not less than 400mm2 ),