1. Conductor DC resistance meet the GB / T3956-2008 required
2.The Properties of Finished Cables Insulation Can meet GB / T12706.1 requirement. And Should Withstand AC Voltage 3.5KV 5Minutes without breakdown.
1.The ambient temperature for installation/Laying is not below 0 ℃, the bending radius should be not less than 10 times of cable diameter.
2.The Long-term Max temperature of Cable Conductor should be not exceed 70 ℃.
3. The Max temperature of Cable Conductor should be not exceed 160 ℃ in short Circuit(the longest duration of no more than 5S and temperature is 140 ℃ when Cable section is not less than 400mm2 )